Turbine-governor models from CGMES
Extends from Modelica.Icons.Package (Icon for standard packages).
| Name | Description |
|---|---|
| CGMES Simplified Hydro Governor |
OpenIPSL.Electrical.Controls.CGMES.TG.GovHydroIEEE0CGMES Simplified Hydro Governor
This diagram is supplied to document the CIM interpretation of the model given in [IEEE1973]. However the general recommondation is to use alternative more sophisticated implementations like HYGOV instead.
| Name | Description |
|---|---|
| K | Governor gain |
| T1 | Governor lag time constant [s] |
| T2 | Governor lead time constant [s] |
| T3 | Gate actuator time constant [s] |
| T4 | Water starting time [s] |
| Pmax | Gate maximum [1] |
| Pmin | Gate minimum [1] |