OpenIPSL.Electrical.Wind.PSSE.WT4G

Model for a Wind Generator with a Back-to-back Interface Converter (Type 4)

Information

Extends from Modelica.Icons.Package (Icon for standard packages).

Package Content

Name Description
OpenIPSL.Electrical.Wind.PSSE.WT4G.WT4G1 WT4G1 Wind Generator Model with Power Converter (Type 4)
OpenIPSL.Electrical.Wind.PSSE.WT4G.WT4E1 WT4E1 Electrical Control for Type 4 Wind Generator

OpenIPSL.Electrical.Wind.PSSE.WT4G.WT4G1 OpenIPSL.Electrical.Wind.PSSE.WT4G.WT4G1

Wind Generator Model with Power Converter (Type 4)

Information

Wind Generator Model with Power Converter WT4G1.

Extends from Icons.VerifiedModel (Icon for classes that were verified), OpenIPSL.Electrical.Essentials.pfComponent (Partial model containing all the parameters for entering power flow data).

Parameters

NameDescription
M_bMachine base power [V.A]
T_IQCmdConverter time constant for I_Qcmd [s]
T_IPCmdConverter time constant for I_Pcmd [s]
V_LVPL1LVPL voltage 1 (Low voltage power logic) [1]
V_LVPL2LVPL voltage 2 [1]
G_LVPLLVPL gain
V_HVRCRHVRCR voltage (High voltage reactive current limiter) [1]
CUR_HVRCRHVRCR current (Max. reactive current at VHVRCR) [1]
RIp_LVPLRate of LVACR active current change [1]
T_LVPLVoltage sensor for LVACR time constant [s]
Power flow data
S_bSystem base power [V.A]
V_bBase voltage of the bus [V]
fnSystem frequency [Hz]
P_0Initial active power [W]
Q_0Initial reactive power [var]
v_0Initial voltage magnitude [1]
angle_0Initial voltage angle [rad]
displayPFDisplay power flow:
Parameter mask
enableS_bEnable S_b in parameter list
enableV_bEnable V_b in parameter list
enablefnEnable fn in parameter list
enableP_0Enable P_0 in parameter list
enableQ_0Enable Q_0 in parameter list
enablev_0Enable v_0 in parameter list
enableangle_0Enable angle_0 in parameter list
enabledisplayPFEnable displayPF in parameter list

Connectors

NameDescription
p 
Iy 
V 
P 
Q 
IyL 
IxL 
I_qcmd 
I_pcmd 
I_qcmd0 
I_pcmd0 

OpenIPSL.Electrical.Wind.PSSE.WT4G.WT4E1 OpenIPSL.Electrical.Wind.PSSE.WT4G.WT4E1

Electrical Control for Type 4 Wind Generator

Parameters

NameDescription
PFAFLGPF fast control
VARFLG 
PQFLAGP/Q priority flag
TfvFilter time constant in voltage regulator [s]
KpvProportional gain in voltage regulator [1]
KIVIntegrator gain in voltage regulator [1/s]
KppProportional gain in torque regulator [1]
KIPIntegrator gain in torque regulator [1]
KfRate feedback gain [1]
TfRate feedback time constant [s]
QMXMax limit in voltage regulator [1]
QMNMin limit in voltage regulator [1]
IPMAXMax active current limit [1]
TRVVoltage sensor time constant [s]
dPMXMax limit in power PI controller [1]
dPMNMin limit in power PI controller [1]
T_PowerPower filter time constant [s]
KQIMVAR/Voltage gain [1]
VMINCLMin voltage limit [1]
VMAXCLMax voltage limit [1]
KVIVoltage/Mvar gain [1]
TvLag time constant in WindVar controller [s]
TpPelec filter in fast PF controller [s]
ImaxTDConverter current limit [1]
IphlHard active current limit [1]
IqhlHard reactive current limit [1]
PSSEMATCH 

Connectors

NameDescription
P 
Q 
V 
WIPCMD 
WIQCMD 
Automatically generated Mon Oct 10 14:35:56 2022.