Records with Turbine-Governor Parameters
Turbine-Governor Data Record Template
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |
Extends from TurbGovernorDataTemplate (Turbine-Governor Data Record Template).
| Name | Description |
|---|---|
| GOV | Governor type (G = general, H = hydraulic, C = cross-compound) |
| R | Turbine steady-state regulation setting or droop [1] |
| P_MAX | Maximum Turbine Output [1] |
| T_1 | Control time constant (governor delay) or governor response time (type H) [s] |
| T_2 | Hydro reset time constant (type G) or pilot valve time (type H) [s] |
| T_3 | Servo time constant (type G or C), or hydro gate time constant (type G) or dashput time constant (type H) [s] |
| T_4 | Steam valve bowl time constant (zero for type G hydrogovernor) or (T_W/2 for type H) [s] |
| T_5 | Steam reheat time constant or 1/2 hydro water setting time constant (type C or G) or minimum gate velocity in MW/s (type H) [s] |
| F | Shaft output ahead of reheater or -2.0 for hydro units (types C or G), or maximum gate velocity in MW/s (type H) [1] |