Test systems used in the Open Cyber-Physical Systems project
OpenCPS project models reported in deliverable D5.3B
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
| Name | Description |
|---|---|
| Base network for testing resynchronization of a generation unit | |
| Extended network for testing resynchronization of a generation unit to a weak grid | |
| Extended network for testing resynchronization of a generation unit to a weak grid under the presence of noise | |
| Models for the generation units used in the test systems | |
| Models for controlled line breakers | |
| Models for control systems used for resynchronization | |
| Models for node injection on electrical nodes |
OpenIPSL.Examples.OpenCPS.NetworkBase network for testing resynchronization of a generation unit
This example system shows how the preparation for resynchronization of Generator 2 to the grid. Note that at 2 seconds, a signal is triggered so voltages between buses 3 and 4 should be equal.
Simulate the system for 10 seconds. Variables of interest are:
B3.vB4.vG1.gen.SPEEDG2.gen.SPEEDNote the behavior of those variables before and after the connection of generator G2 to the main grid.
Extends from Modelica.Icons.Example (Icon for runnable examples).
OpenIPSL.Examples.OpenCPS.Network_ExpandedExtended network for testing resynchronization of a generation unit to a weak grid
This example system shows how the resynchronization controller is used to connect Generator 2 back to the grid. Note that at 2 seconds, a signal is triggered to equalize voltage magnitudes on buses 3 and 4.
Simulate the system for 50 seconds. Variables of interest are:
B3.vB4.vG1.gen.SPEEDG2.gen.SPEEDNote the behavior of those variables before and after the connection of generator G2 to the main grid.
Extends from Modelica.Icons.Example (Icon for runnable examples).
OpenIPSL.Examples.OpenCPS.Network_Expanded_NoiseExtended network for testing resynchronization of a generation unit to a weak grid under the presence of noise
This example system shows how the resynchronization controller is used to connect Generator 2 back to the grid even under the presence of noise. Note that at 2 seconds, a signal is triggered to equalize voltage magnitudes on buses 3 and 4.
Simulate the system for 50 seconds. Variables of interest are:
BG1.vB4.vG1.gen.SPEEDG2.gen.SPEEDNote the behavior of those variables before and after the connection of generator G2 to the main grid.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Automatically generated Thu Oct 6 17:41:43 2022.